SPECIFICATION
Section 09546 - Metal Plank  Acoustical Security Ceiling System
1.0  SCOPE OF WORK 
1.1 WORK INCLUDED: This specification  covers the material, installation, and related requirements for the Metal Plank  Ceiling System - including all necessary acoustical insulation, suspension  systems, and fasteners.
1.2 RELATED WORK: The following items of related  work are not included in this Section of the specifications.
1.2.1 Ceiling Lighting Systems; their  components, layout, coordination, installation, or support systems. Compatible  recessed Security Lighting Fixtures are to be furnished and installed by  Division 16 Electrical.
1.2.2 Ceiling Air Supply and Return  Systems; their components, layout, coordination, installation, or support  systems. Compatible air supply and return systems are to be furnished and  installed by Division 15 Mechanical.
2.0  SUBMITTALS
2.1 A manufacturer's certification of  compliance with the acoustical performance required under Section 6.2 of this  specification.
2.2 After award of contract Shop  drawings shall be submitted and approved prior to fabrication of the ceiling  panels or their structural supports.
2.3 A 1' x 1' assembled sample of each  ceiling panel and its suspension system shall be submitted for approval.
2.4 Manufactures' Product Data and  Installation Instructions.
3.0  FIELD CONDITIONS: The ceiling contractor  shall verify all dimensions, elevations, and job site conditions before  fabrication commences.
4.0 PRODUCT COMPONENTS 
4.1 METAL PLANK CEILINGS: The Metal Plank Ceiling System is to be fabricated and  installed in accordance with the manufacturers approved shop drawings. Metal  planks shall be factory formed from 14) (16) gauge perforated  (non-perforated) galvannealed A60 steel as indicated on the drawings.  Planks shall be formed (12") (18") (24") wide in lengths of up  to 12'-0" as shown on reflected ceiling plans. Vertical legs of metal planks are to be  factory formed so that panels interlock tightly to provide positive  self-alignment with adjacent panels.
4.2 METAL PLANK SUSPENSION: Perimeter angles and main tee  runners shall be factory fabricated from 12) gauge factory finished  galvannealed (min. A60) steel. Angles and tees shall be factory prepunched  to receive fasteners. Angles shall be fastened to all abutting vertical  surfaces through the use of drilled in anchors or other approved fasteners at a minimum of 24" O/C. Tee sections shall be suspended by 3/8”  dia threaded rods with adjustable yokes pinned to main tees at minimum  of 3'-0" O.C., hung from structural members as approved by the  architect. Panels shall be securely fastened to all angles and tee sections  with steel pop rivets or security fasteners of appropriate dimension (painted to  match panels) minimum 12" on center.
4.3 ACOUSTICAL MATERIAL: The inside surface of all perforated  ceiling panels shall be covered with Class "A" fiberglass  insulation wrapped in black Fire Retardant Poly. Insulation shall be of  sufficient thickness and density to provide the acoustical requirements as  outlined in Section 6.2 of this specification.
4.4 LIGHTS AND AIR: Although not furnished by the ceiling  system manufacturer, all light and air units are to be system compatible and  sized so as to fit into and trim off full module opening in ceiling system and  shall be independently supported from above by installing trade.
4.5 ACCESS  DOORS: All security access doors to be installed in the Metal Plank Ceiling  System shall be supplied by the Metal Plank Ceiling System manufacturer in  quantities indicated on the architectural drawings or as approved by the  architect.
ACCESS DOORS SHALL HAVE THE FOLLOWING CHARACTERISTICS:
Sizes in Inches: 12x12, 18x18, 18x24 or 24x24
Door Construction: 14 gauge steel.
Frame Construction: 12 gauge steel.
Hinge: Full-length semi-concealed piano hinge. Opens 180 degrees.
Anchors: 1/4-20 Torx fasteners.
Lock: 1/4-20 Torx fasteners (or optional keyed deadlock).
Finish: Factory White Polyester Powder Coated Paint finish.
4.6 FASTENERS: All exposed fasteners shall be tamper proof and  shall be a minimum #10 size. Fasteners for securing the wall molding to the wall  are to be selected and furnished by the contractor and approved by the  architect/engineer.
5.0 FINISH
5.1 METAL PLANKS AND RELATED SUSPENSION: The  metal planks shall have a factory White Polyester Powder Coated Paint finish.  Finish to be applied after perforation to insure coating of perforated holes.  Panels shall be coated with white polyester powder to a finish side thickness  min. 2.0 mil. Prior to painting, galvanealled steel or aluminum surfaces shall  be cleaned, rinsed, and properly treated to receive the powder finish. Finish  to achieve the following performance characteristics: Salt Spray per ASTM B-117  - 1000 hours PASS at less than 1/8" from score; Humidity Resistance per  ASTM D-2247 - 1000 hours PASS at less than 1/8" from score.
6.0  PERFORMANCE 
6.1 ACCESSIBILITY: Suspended metal plank  ceiling systems shall be designed and installed to resist access to the plenum  area. System compatible hinged locking downward accessible doors are to be  provided in locations indicated on architectural reflected ceiling plans.  Access Doors are to be sized so as to fit into and trim off full module opening  in ceiling system.
    
6.2 ACOUSTICAL REQUIREMENTS: The  perforated ceiling systems shall provide a noise reduction co-efficient (NRC)  of no less than 0.80 when tested in accordance with ASTM C423-84a in an E-400  mounting as defined in ASTM E795-83.
7.0 MATERIAL PROTECTION AND INSTALLATION
7.1 MATERIAL PROTECTION: Material shall not be delivered to the  job site, nor installed, until all exterior openings have been closed in and  all concrete and other wet work is completed and dry.
7.2 SITE INSPECTION: Prior to installation of the ceiling  systems, the general contractor shall verify that the structure and surfaces  provided by other trades are properly built to the dimensions shown on the  approved ceiling shop drawings and that the structure is ready to receive the  ceiling system. All discrepancies shall be corrected prior to commencing  installation.  
7.3 INSTALLATION: The ceiling systems shall be installed in  accordance with ASTM C636, and CISCA guidelines, in layouts as reflected on the  approved shop drawings, all in compliance with the manufacturer's installation  instructions. The suspension system and wall moldings shall be installed plumb  and level. Start installation of Metal Plank at location as shown on reflected  ceiling plans. Slide Metal Plank along perimeter angle to create a interlocking  joint between adjoining panels. Insure self-aligning legs overlap each other.  Side stitch panels together along interlocked panel joins with self tapping  fasteners per approved shop drawings or at a minimum of 24" o/c. In  order to achieve secure and tightly engaged panel joint details, panels must be  installed progressively from the start panel through the closure panel. Except  for the openings for light, air, fire protection, or access shown on the  reflected ceiling plans, all openings or cut outs required in the ceiling  planks shall be field cut by the trades requiring the openings.
8.0 QUALITY ASSURANCE 
8.1 MANUFACTURER QUALIFICATIONS: Company specializing and  regularly engaged in the domestic manufacture of metal plank security ceilings  with a minimum of ten (10) years experience in the manufacture of  correctional ceiling systems.
8.2 ERECTOR QUALIFICATIONS: Company specializing in the  installation of metal plank security ceilings, approved by the manufacturer,  and having a minimum of three (3) years experience in the installation  of correctional ceiling systems.
8.3 SINGLE  SOURCE RESPONSIBILITY: To insure proper compatibility, all ceiling components  listed in Section 4.0 Product Components, shall be provided by a single source.
9.0 ACCEPTABLE MANUFACTURERS  
9.1 SUSPENDED METAL SECURITY PLANK CEILING SYSTEM: Shall be DetentionGRADE tm  as manufactured  by Detention Device Systems, Hayward,  California 94545 510 7830771 or as approved by architect in accordance with Paragraph 9.2  below.
9.2 SUBSTITUTIONS: Ceiling systems by other manufacturers may  be substituted only after written approval of the architect, such approval  being received ten (10) calendar days prior to the bid opening. The proposed  system shall meet all the requirements of this specification. 